Troubleshooting Guide
102 Universal System Air Conditioner
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal
• Check the connecting condition of CN-U/D or CN0L/R Connector
• Check the soldering condition(on PCB) of CN-U/D or CN0L/R Connector
Check the operating circuit of the vertical louver
• Confirm that there is DC +12V between pin ➀ of CN-U/D, CN0L/R and GND.
• Confirm that there is a soldering short at following terminals.
- Between 1 ,  2 ,  3 and  4 of MICOM - Between  
17
,  
18
,  
19
and  
20
of MICOM
- Between  
4 ,  5
,  6 and  7 of IC01M - Between  5 ,  6 ,  7 and  8 of IC01M
When the louver does not operate.
Trouble 5
If there are no problems after above checks.
• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver