Troubleshooting Guide
96 Universal System Air Conditioner
■ Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
Error code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
00 No Error ON
01 Indoor Room themistor error 1time  OFF
02 Indoor in-piping sensor error 2times  OFF
03 Remote controller error 3times  OFF
04 Drain Pump error 4times  OFF
05 Communcation error between in and out 5times  OFF
06 Indoor Out-Piping sensor error 6times  OFF
07 Differnt mode operation 7times  OFF
Outdoor Error
Error Code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
21 DC Peak (IPM Fault) 2times  1time  OFF
22 CT 2(Max CT) 2times  2times  OFF
23 DC Link Low Volt. 2times  3times  OFF
24 L_P/Heater Sink 2times  4times  OFF
25 Low voltage / Over voltage 2times  5times  OFF
26 DC Comp Position Error 2times  6times  OFF
27 PSC Fault Error 2times  7times  OFF
28 DC Link High Volt 2times  8times  OFF
32 D-Pipe High (INV) 3times  2times  OFF
33 D-Pipe High (Normal) 3times  3times  OFF
40 CT Sensor (Open/Short) 4times  O OFF
41 INV. D-PipeTh Error(Open/Short) 4times  1time  OFF
44 Outdoor air Th Error(Open/Short) 4times  4times  OFF
45 Cond. Pipe Th Error(Open/Short) 4times  5times  OFF
46 Suction Pipe Error(Open/Short) 4times  6times  OFF
47 Const D-pipe Th Error(Open/Short) 4times  7times  OFF
51 Capacity over 5times  1time  OFF
53 Signal error (Indoor ↔ Outdoor) 5times  3times  OFF
60 EEPROM Check Sum Error 6times  O OFF
61 Cond. Pipe High 6times  1time  OFF
62 Heatsink High 6times  2times  OFF
63 Cond. Pipe Low 6times  3times  OFF
65 Heatsoml Th error (Open/Short)
6times  5times  OFF
Self-diagnosis Function