Ceiling Concealed Duct
50 Universal System Air Conditioner
Conversion Formula
kW = Btu/h × 0.0002931
kcal/h = Btu/h × 0.252
CFM = CMM × 35.3
Power Supply Ø/V/Hz
Cooling Capacity kW
Btu/h
Heating Capacity kW
Btu/h
Current Nominal running current A
Fan Motor Type
Fan Type
Motor Output x Number of Unit
Air Flow Rate(H/M/L) cmm
cfm
External Static Pressure mmAq
Capacitor µF/Vac
Drive
Coil Row x Columns x FPI mm
Dimensions(WxHxD)
Body mm(inch)
Weight Body kg(lbs)
Air Filter
Sound Level (H/M/L) dB(A)+3
Piping Liquid mm(inch)
Connections Gas mm(inch)
Drain(OD/ID) mm
Dehumidification Rate l/h
Safety devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable outdoor unit
Power and transmission interunit cable No.x mm
2
Model
ABNH366GLAB
[UB36 NGB]
ABNH486RLAB
[UB48 NRB]
ABNH606RLAB
[UB60 NRB]
Indoor unit type Ceilling Concealed Duct - High Static
1 / 220 ~240 / 50 1 / 220 ~240 / 50 1 / 220 ~240 / 50
10.6 14.1 16.4
36,000 48,000 56,000
12.1 15.5 18.1
41,400 52,800 61,600
1.42 3.65 3.65
Induction Induction Induction
Sirocco Fan Sirocco Fan Sirocco Fan
272*2 431*2 431*2
32/29/26 40/35/30 50/45/40
1130/1024/918 1413/1236/1059 1766/1413/1236
10 15 15
6/370 15/450 15/450
Direct Drive Direct Drive Direct Drive
3R x 10C x 21 3R x 13C x 19 4R x 13C x 19
1180*298*450(46.5*11.7*17.7) 1230*380*590(48.4*15.0*23.2) 1230*380*590(48.4*15.0*23.2)
38(84) 60(132) 60(132)
Long life filter Long life filter Long life filter
42/39/36 44/42/40 46/44/42
6.35 (1/4) 9.52(3/8) 9.52(3/8)
15.88(5/8) 19.05(3/4) 19.05(3/4)
32/25 32/25 32/25
4.0 6.0 6.5
Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Thermistor Thermistor Thermistor
R-410A R-410A R-410A
LEV LEV LEV
Single A Single A Single A
4*0.75 4*0.75 4*0.75
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Cooling/heating capacity of indoor unit can be lower when it is connected to MPS variable outdoor.
3. Wiring cable size must comply with the applicable local and national code.