Ceiling Concealed Duct
56 Universal System Air Conditioner
Table 7-1
Static Pressure(mmAq)
Setting Value
0246810121415
Model Name
Step CMM(CFM)
High 16.5(583) 235 230 225 215 180
Med 14.5(512) 245 238 235 230 215
Low 13(459) 254 252 248 245 240
High 18(636) 220 205 190 50 1
Med 16.5(583) 235 230 220 200 100
Low 14(494) 250 240 235 230 210
High 26.5(936) 153 150 150 148 130 1
Med 23(812) 173 173 175 175 170 155
Low 20(706) 190 190 190 190 190 190
High 32(1130) 230 230 225 220 150 1
Med 29(1024) 240 238 237 235 230 220
Low 26.5(936) 245 245 243 243 240 240
High 40(1412) 230 225 220 215 205 200 190 180 160
Med 35(1235) 250 245 240 235 230 220 215 210 200
Low 30(1059) 255 255 255 250 245 240 235 230 225
High 50(1766) 185 180 174 162 154 140 90 5 1
Med 45(1589) 210 205 199 191 189 180 155 138 110
Low 40(1423) 230 225 219 215 210 205 193 180 171
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 7-1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
ABNH186HLAB
[UB18 NHB]
ABNH246HLAB
[UB24 NHB]
ABNH306GLAB
[UB30 NGB]
ABNH366GLAB
[UB36 NGB]
ABNH486RLAB
[UB48 NRB]
ABNH606RLAB
[UB60 NRB]