EasyManua.ls Logo

LG Universal System Air Conditioner - Page 94

LG Universal System Air Conditioner
183 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94 Universal System Air Conditioner
MPS Inverter SINGLE A
8.4 Piping length and the elevation
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.
CAUTION
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
Gas Liquid Standard Max. Standard Max.
Capacity
18k Btu/h
1/2"
(12.7mm)
1/4"
(6.35mm)
7.5 40 5 30
25
12k Btu/h
1/2"
(12.7mm)
1/4"
(6.35mm)
7.5 40 5 30 20
24k Btu/h
1/2"
(12.7mm)
1/4"
(6.35mm)
7.5 50 5 30 30
30k Btu/h
5/8"
(15.88mm)
1/4"
(6.35mm)
7.5 50 5 30 35
36k Btu/h
Extra refrigerant = (Extended length - Rated length) x Additional refrigerant.
5/8"
(15.88mm)
1/4"
(6.35mm)
7.5 50 5 30 35
48k Btu/h
3/4"
(19.05mm)
3/8"
(9.52mm)
7.5 70 5 30
50
(Chargeless 30m)
60k Btu/h
3/4"
(19.05mm)
3/8"
(9.52mm)
7.5 70 5 30
50
(Chargeless 30m)
Pipe Size
Length (m) Elevation (m)
*Additional
(Diameter:Ø)
refrigerant(g/m)

Table of Contents

Related product manuals