Specifications
30 Liebert
®
InteleCool
®
2
Table 15 Optional heater capacity, 50 Hz
Nominal Heater Rating
Heater Capacity - kW
3 Ton 4 Ton 5 Ton
5 kW
Capacity @ 220V-1ph 4.201 4.201 4.201
Capacity @ 240V-1ph 5.000 5.000 5.000
Capacity @ 200V-3ph 3.472 3.472 3.472
Capacity @ 230V-3ph 4.592 4.592 4.592
Capacity @ 240V-3ph 5.000 5.000 5.000
Capacity @ 380V-3ph 4.192 4.192 4.192
Capacity @ 415V-3ph 5.000 5.000 5.000
10 kW
Capacity @ 220V-1ph 8.403 8.403 8.403
Capacity @ 240V-1ph 10.000 10.000 10.000
Capacity @ 200V-3ph 6.944 6.944 6.944
Capacity @ 230V-3ph 9.184 9.184 9.184
Capacity @ 240V-3ph 10.000 10.000 10.000
Capacity @ 380V-3ph 8.384 8.384 8.384
Capacity @ 415V-3ph 10.000 10.000 10.000
15 kW
Capacity @ 220V-1ph 12.604 12.604 12.604
Capacity @ 240V-1ph 15.000 15.000 15.000
Capacity @ 200V-3ph 10.417 10.417 10.417
Capacity @ 230V-3ph 13.776 13.776 13.776
Capacity @ 240V-3ph 15.000 15.000 15.000
Capacity @ 380V-3ph 12.577 12.577 12.577
Capacity @ 415V-3ph 15.000 15.000 15.000