Specifications
Liebert
®
InteleCool
®
231
Table 16 Electrical data, 60 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0187 208/230 1 14.5 17.2 25 23.4 29.3 30 44.4 55.5 60 NA — — — — —
ET0247 208/230 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA — — — — —
ET0247 208/230 3 12.4 14.6 20 14.4 18 20 26.4 33 35 NA — — — — —
ET0247 460 3 5.9 6.9 15 7.3 9.1 15 13.3 16.6 20 NA — — — — —
ET0367 208/230 1 20.9 25.2 40 23.4 29.3 40 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0367 208/230 3 15.8 18.8 30 15.8 18.8 30 26.4 33 35 38.4 48 50 — — —
ET0367 460 3 8.4 10 15 8.4 10 15 13.3 16.6 20 19.3 24.1 25 — — —
ET0487 208/230 1 31.9 38 50 31.9 38 50 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET0487 208/230 3 24.7 29 35 24.7 29 35 28.2 35.3 35 40.2 50.3 60 — — —
ET0487 460 3 11.7 13.7 20 11.7 13.7 20 14.1 17.6 20 20.1 25.1 30 — — —
ET0607 208/230 1 37.7 45.2 60 37.7 45.2 60 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET0607 208/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50 — — —
ET0607 460 3 13.8 16.3 25 13.8 16.3 25 14.1 17.6 25 20.1 25.1 30 — — —
* 15 kW heat option @ 208/230 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.
Table 17 Electrical data, 50 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0357 220/240 1 18.1 21.7 35 23.4 29.3 35 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0357 200/230 3 15.8 18.8 25 15.8 18.8 25 26.4 33 35 38.4 48 50 — — —
ET0357 380/415 3 8.4 10.0 15 8.4 10.0 15 15.3 19.1 20 22.3 27.9 30 — — —
ET0477 200/230 3 23.3 27.2 35 23.3 27.2 35 28.2 35.3 35 40.2 50.3 60 — — —
ET0477 380/415 3 11.7 13.7 20 11.7 13.7 20 16.1 20.1 25 23.1 28.9 30 — — —
EF0597 200/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50 — — —
ET0597 380/415 3 13.8 16.3 25 13.8 16.3 25 16.1 20.1 25 23.1 28.9 30 — — —
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.