Chapter 3 Disassembling Electrical Parts 11
Liebert.PEX+Series Precision Air Conditioner Dissassemble Manual
输入功率电缆
输入控制信号电缆
风机过热信号电缆
输出功率电缆
Input control signal cables
Over temperature signal
cables of fan
Output power cables
Input power cables
Figure 3-6 Illustration for the cables of the VSC03Z control fan assembly
Note
No need to disassemble the input power cables and input control signal cables, however, in order to avoid the
risk of pulling the cables of VSC03Z, you can disassemble these cables from the VSC03Z board.
The connection cables between VSC03Z and the fan are the output power cables and fan over temperature
signal cables be sure to disassemble them before disassembling the fan.
When restoring the cables, be sure to install the OT terminal of the output power cables according to the
factory standard.
3.8 Disassembling the cables of EBM fan assembly
The cables of EBM fan assembly are shown in Figure 3-7.
功率电缆
信号电缆
power cables
signal cables
Figure 3-7 Illustration for the cables of EBM fan assembly
Note
When restoring the cables, be sure to re-bind the cable ties according to the factory standard.
3.9 Disassembling the cables in cable chute and pipes
After completing the steps 3.1-3.8, pull out the cables from the cable chute and pipes of the electric control cabinet.
Pull out the cables connected to the refrigerating cabinet and put the cables inside the cabinet. Do not put the cables
outside of the cabinet to avoid damaging the cables during transportation process.