UPSTATION GXT BATTERY RUN TIMES
(Discharge times are at 25° C ambient)
Internal Battery (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% 52 95 95 170 80 160 101
20% 38 46 46 128 40 83 51
30% 30 33 33 95 29 47 28
40% 23 26 26 70 21 34 20
50% 16 19 19 50 15 27 15
60% 12 14 14 37 11 21 12
70% 10 12 12 29 9 18 10
80% 8 9 9 24 7 15 8
90% 7 8 8 20 6 13 7
100% 5 7 7 18 5 11 6
Internal Battery + 1 External Battery Cabinet (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% N/A N/A 479 554 408 343 273
20% N/A N/A 255 337 215 204 140
30% N/A N/A 150 212 125 133 78
40% N/A N/A 110 154 95 100 57
50% N/A N/A 85 116 75 77 44
60% N/A N/A 66 89 57 60 35
70% N/A N/A 56 73 48 50 30
80% N/A N/A 48 63 40 43 26
90% N/A N/A 41 53 35 36 22
100% N/A N/A 35 46 29 31 18
Internal Battery + 2 External Battery Cabinets (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% N/A N/A 848 923 718 623 444
20% N/A N/A 425 507 365 345 236
30% N/A N/A 243 305 208 211 138
40% N/A N/A 196 240 164 156 100
50% N/A N/A 168 199 139 120 75
60% N/A N/A 133 156 112 94 59
70% N/A N/A 109 126 94 81 50
80% N/A N/A 89 104 78 70 43
90% N/A N/A 77 89 68 62 36
100% N/A N/A 66 77 58 54 31