15
2022-07-19
SEF Mode:
Pressure
AFA in system
No_
SEF Mode:
Pressure
AFA in system
Yes_
SEF Mode:
Pressure
AFA in system
Yes
SEF Setpoint:
Fire: 80 Pa
Excercise: 110 Pa
Support: 50 Pa
Adressing Slaves
-> SEF
Communication
De-/Activate Damper
Pressure sensor
enabled: No_
Current pressure
0 Pa
Pressure sensor
enabled: No
Current pressure
0 Pa
De-/Activate Damper
Detector/Temp AI1
-> Pressure sensor
Miscellaneous
Pressure sensor
enabled: Yes_
Current pressure
0 Pa
Pressure sensor
enabled: Yes
Current pressure
0 Pa
Detecotr/Temp AI1
Pressure sensor
Miscellaneous
-> System activate
->Adressing Slaves
SEF
Communication
De-/Activate Damper
Status Overview
-> System Setup
Settings
Manual/Auto
Activate
system: Install
Activate
system: Install_
Activate
system: Run_
Activate
system: Run
lindab | commissioning guide
We reserve the right to make changes without prior notice
FireSystemPro
7. Press ”OK” to confirm
SEF mode.
8. Press ”up” to activate
AFA in system
(fire panel).
9. Press ”OK” to confirm
AFA system activation
10. Press ”down” to set
points and setups for
SEF
11. Press ”back” to go
back to ”System Setup”
12. Press ”down” to find
Pressure sensor”
13. Press ”forward”
to enter ”Pressure
sensor”
14. Press ”OK” to edit
”Pressure sensor ena-
bled”
15. Press ”up” to
change status for ”Pres-
sure sensor enabled” to
YES
16. Press ”OK” to
confirm AFA system
activation
SEF mode is now setup
2.11 Activate the Fire System Pro
1. Press ”down” to find
”System Setup”
2. Press ”forward” to
enter ”System Setup”
3. Press ”down” to find
”System activate”
4. Press ”forward”
to enter ”System
activate”
5. Press ”OK” to edit
”Activate System”
6. Press ”up” to change
status to RUN
5. Press ”OK” to
confirm status for
”Activate System”
The Fire System Pro is now activated and running
SEF mode (cont.)