inputs S1 to S3. (Default: NPN mode)
Figure 4.4.1.1 <5.5Kw series Sink/Source DIP Switch
Figure 4.4.1.2 >7.5Kw series Sink/Source DIP Switch
4.4.2 Terminal A2 Voltage/Current Input Selection
Select voltage or current input at terminal A2
◼ To select current as the input type, set DIP switch A2 to I and set parameter E3-06 to 0 (0 to 20
mA) or 1 (4 to 20 mA).
To select voltage as the input type, set DIP switch A2 to V and set parameter E3-06 to 2 (0 to 10 V) or
3 (0 to 5 V).