79
5.2 Parameter List
Parameter
Name
Description
Setting Range
Group A, Initialization
A1: Basic Settings
A1-00
Retain
A1-01 <4>
Access Level
Selection
Selects access level ( edit /view)
0: View Only
Access to only parameter A1-01
1: User-Defined Parameter Access
Access to only parameter A1-01 and A2-00
to A2-31
2: All Parameter Access
All parameters can be edited and viewed
Default 2
Min.: 0
Max.: 2
A1-02
Control Method
Selection
0: V/F Control
1: Senserless Voltage Vector Control
Default: 0
Range: 0 to 1
A1-03
Reset
Resets parameter settings to defaults. After resetting
parameters, the value will become 0.
2520: Resets 2-Wire Sequence/ 50Hz / 200V
2522: Resets 2-Wire Sequence/ 50Hz / 220V
2523: Resets 2-Wire Sequence/ 50Hz / 230V
2524: Resets 2-Wire Sequence/ 50Hz / 240V
2538: Resets 2-Wire Sequence/ 50Hz / 380V
2541: Resets 2-Wire Sequence / 50Hz / 415V
2544: Resets 2-Wire Sequence / 50Hz / 440V
2546: Resets 2-Wire Sequence / 50Hz / 460V
2548: Resets 2-Wire Sequence/ 50Hz / 480V
2620: Resets 2-Wire Sequence/ 60Hz / 200V
2622: Resets 2-Wire Sequence/ 60Hz / 220V
2623: Resets 2-Wire Sequence/ 60Hz / 230V
2624: Resets 2-Wire Sequence/ 60Hz / 240V
2638: Resets 2-Wire Sequence / 60Hz / 380V
2641: Resets 2-Wire Sequence / 60Hz / 415V
2644: Resets 2-Wire Sequence / 60Hz / 440V
2646: Resets 2-Wire Sequence / 60Hz / 460V
2648: Resets 2-Wire Sequence/ 60Hz / 480V
3520: Resets 3-Wire Sequence/ 50Hz / 200V
3522: Resets 3-Wire Sequence/ 50Hz / 220V
3523: Resets 3-Wire Sequence/ 50Hz / 230V
3524: Resets 3-Wire Sequence/ 50Hz / 240V
3538: Resets 3-Wire Sequence / 50Hz / 380V
3541: Resets 3-Wire Sequence / 50Hz / 415V
3544: Resets 3-Wire Sequence / 50Hz / 440V
3546: Resets 3-Wire Sequence / 50Hz / 460V
3548: Resets 3-Wire Sequence/ 50Hz / 480V
3620: Resets 3-Wire Sequence/ 60Hz / 200V
3622: Resets 3-Wire Sequence/ 60Hz / 220V
3623: Resets 3-Wire Sequence/ 60Hz / 230V
3624: Resets 3-Wire Sequence/ 60Hz / 240V
3638: Resets 3-Wire Sequence / 60Hz / 380V
3641: Resets 3-Wire Sequence / 60Hz / 415V
3644: Resets 3-Wire Sequence / 60Hz / 440V
3646: Resets 3-Wire Sequence / 60Hz / 460V
Default: 0
Range: 9999