EasyManua.ls Logo

LiteOn EVO 6800 Series - I;O Connections

LiteOn EVO 6800 Series
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
Table 4.3.2.2 Cable Size and Tightening Torque (>7.5kW models)
Terminal
Screw Size
Tightening
Torque
Nm
( lb.in.)
Bare Cable
Ferrule-Type Terminal
Cable Type
Applicable
Size
mm
2
( AWG)
Suggested
Size
mm
2
( AWG)
Applicable
Size
mm
2
( AWG)
Suggested
Size
mm
2
( AWG)
AC,V+,FM,A1,AM,A2,24V,S1,
S2,S3,S4,S5,S6,S7,COM,S7C,
D+,MP,D-DC,PE,D1
M2.5
0.59
(5.2)
0.13 ~ 1.31
(26 ~ 16)
0.13
(26)
0.13 ~ 0.33
(26 ~ 22)
0.13
(26)
Shielded
cable, etc.
R1A,R1B,R1C,R2A,R2C
M2.5
0.59
(5.2)
0.2 ~ 3.31
(24 ~ 12)
0.2
(24)
0.2 ~ 0.33
(24 ~ 22)
0.2
(24)
Shielded
cable, etc.
4.3.3 Ferrule-Type Terminals
Always use ferrule-type terminals with insulated sleeves. Refer to Table 4.3.3.2. for dimensions. In
addition, crimping tool CRIMPFOX ZA-3 manufactured by Phoenix Contact is recommended.
Table 4.3.3.2 Ferrule-Type Terminal Models and Sizes
Cable Size
mm
2
( AWG)
Type
L
( mm)
d1
( mm)
d2
( mm)
Manufacturer
0.25 ( 24)
AI 0.25-6YE
10.5
0.8
2
Phoenix Contact
0.34 ( 22)
AI 0.34-6TQ
10.5
0.8
2
Phoenix Contact
0.5 ( 20)
AI 0.56-WH
14
1.1
2.5
Phoenix Contact
4.4 I/O Connections
4.4.1 NPN and PNP Mode Selection
Use Sink/Source DIP switch on the control board to set NPN/PNP mode for multi-function digital