68
4.4.3 Terminal AM Voltage/Current Output Selection
Select voltage or current output type for terminal AM
To select voltage as the output type, set DIP switch AM to V and set parameter E4-04 to 0 (0 to
10 V) .
To select current as the output type, set DIP switch AM to I and set parameter E4-04 to 1 (0 to
20 mA) or 2 (4 to 20 mA).
Figure 4.4.3 DIP Switch AM
Table 4.4.3 DIP Switch AM Setting (Terminal AM)
Setting
Description
V
Voltage output (0 to 10 V)
I
Current output (4 to 20 mA or 0 to 20 mA) (default)
Table 4.4.4 Parameter 4-04
No
Parameter Name
Description
Setting
Range
Default
E4-04
Terminal AM Signal
Level Selection
Selects the signal level for terminal
AM
0 : 0 to 10 V
1 : 0 to 20 mA
2 : 4 to 20 mA
0, 1, 2
2