4.4.3 Terminal AM Voltage/Current Output Selection
Select voltage or current output type for terminal AM
◼ To select voltage as the output type, set DIP switch AM to V and set parameter E4-04 to 0 (0 to
10 V) .
◼ To select current as the output type, set DIP switch AM to I and set parameter E4-04 to 1 (0 to
20 mA) or 2 (4 to 20 mA).
Figure 4.4.3 DIP Switch AM
Table 4.4.3 DIP Switch AM Setting (Terminal AM)