Description of terminal connections:
DC power supply. Connected with negative of starter
battery.
DC power supply. Connected with positive of starter
battery. If wire length is over 30m, better to double
wires in parallel. Max. 20A fuse is recommended.
B+ is supplied by 2 point, rated 5A.
B+ is supplied by 2 point, rated 5A. Connect to starter
coil.
B+ is supplied by 2 point, rated 5A.
B+ is supplied by 2 point, rated 5A.
Ground connected is active (B-) .
Connect to a
temperature/cylinder
resistance sensor.
Connect to a oil pressure
resistance sensor.
Outside connected to secondary coil of current
transformer(rated 5A)
See INSTALLATION in the manual.
Connect to speed sensor; Shielded wire is
recommended.
The other end of speed sensor connects to B-.
Connect to charging starter’s D+ terminal. If there is no
this terminal, then be hang up.
The combination of terminal 19 and 21 is relay normally
open contact; rated 5A; Voltage free.
The combination of terminal 20 and 21 is relay normally
open contact; rated 5A; Voltage free.
Common terminal of auxiliary output 4 and 5.
Connected to U-phase of generator (2A fuse is
recommended)