If the generator without magnetoelectric sensor and Oil pressure sensor,the“Charger D+”is optional
as a starter motor separation conditions.It is recommended to select“Oil Pressure+ Charger D+”for
safety.
When reselect sensors, the sensor curve will be transferred into the standard value.
When there is difference between standard sensor curves and the using sensor, user can adjust it in
“curve type ” via PC. After the adjustment is completed, the data will be saved to the "custom
resistance curve" option.Using a custom sensor when choosing the sensor options "Custom
resistance curve."
In the control panel, the same can customize the sensor curve, such as setting the project is "85.
Custom sensor curve."
The specific operation as follows:
1
Switch to【85 custom sensor curve】interface.
2
Press key to enter the sensor type selected, press to switch type.
3 Select Custom sensor curve type, pass button to enter the data setting interface.
4
After setting, press button to return to the previous menu.
If select sensor type as “None”, sensor curve is not working and LCD display “---” for the sensor
If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil
pressure sensor as “None”, otherwise, maybe low oil pressure shutdown occurs.