Code COMMAND ACCESS LEVEL DESCRIPTION
C.01 RESET HI-LO User / Advanced Resets the HI and LO values of all measurements
C.02 RESET MAX DEMAND User / Advanced Resets Max Demand values for all measurements
C.03 RESET PARTIAL ENERGY METERS User / Advanced Resets partial energy meters
C.04 RESET PARTIAL HOUR COUNTER User / Advanced Resets partial hour counters
C.07 RESET ALARMS User / Advanced Resets alarms with latch
C.08 RESET LIMITS User / Advanced Resets limit thresholds with latch
C.11 RESET TOTAL ENERGY METER Advanced Resets total and partial energy meters
C.12 RESET TOTAL HOUR COUNTERS Advanced Resets total hour counters
C.13 PARAMETERS TO DEFAULT Advanced Restores all settings to factory default values
C.14 PARAMETER BACKUP Advanced Saves a backup copy of the settings
C.15 PARAMETERS RESTORE Advanced Reloads the settings from the backup copy
C.16 WIRING TEST Advanced Runs the test to check that the DMG is connected correctly.
See Connection Test section
COMMANDS MENU
The commands menu permits the execution of occasional operations such as resetting measurements, meters, counter, etc.
If the advanced-access password has been entered, the commands menu can also be used to perform some automatic operations that are useful for configuring the instrument.
The following table indicates the functions available through the commands menu, divided by required access level.
Once the desired command is selected, press to execute it. The instrument will request confirmation. Pressing again will execute the command.
To cancel the execution of a selected command, press MENU.
To abandon the command menu, press MENU.
CONNECTION TEST
The connection test permits verification of the correct installation of the multimeter.
In order to run the test, the multimeter must be connected to an active system with the following conditions:
three-phase system with all phases present (V > 50VAC PH-N)
minimum current flow in each phase > 1% of the CT full scale set
positive flow of energies (i.e. a normal system where the inductive load draws power from the supply)
To launch the test, enter the commands menu and select command C.16, according to the instructions in the Commands Menu section.
The test permits verification of the following:
reading of the three voltages
phase sequence
voltage unbalance
reverse polarity of one or more CTs
mismatch between voltage/current phases
If the test is not passed, the display shows the reason for the failure.