Chapter 7. Usage of Various Functions
7-35
SV setting (G7E-RD2A): 1300(60°C ),1350(70°C ),1400(80°C ),1500(100°C)
Current value setting: %MW4104 (Digital value of RTD module Ch 0, expansion module #2)
BIAS setting: 0 (If only P control is used, input proper value other 0)
Mode Command Set: select the related items Derivative, Integral, Proportional (select PWM when it is needed)
PWM contact: When it is activated, input proper values.
SV Ramp: 500 (when SV converted‘500*0.5 sec = 25 sec’)
ΔMV : 4000 (delta MV function is not used)
PID Algorithm: Velocity
c) RTD module setting
Channel setting: channel 0
RTD type setting : Pt100
Digital conversion data registration area: %MW4104
d) D/A module setting
Channel setting: channel 0
Output range setting: DC 4 ~ 20 mA
D/A conversion data registration area: %MW4100