Chapter 7. Usage of Various Functions
7-66
6) Digital/Analog conversion characteristics
(1) G7F-DA2I
a) 0~20mA output
Digital amount 0 outputs analog amount 0mA, 4000 does 20mA.Digital input 1 equals to 5 of analog amount.
b) 4~20mA output
Digital amount 0 outputs analog amount 4mA, 4000 does 20mA.Digital input 1 equals to 6.25 of analog amount.
(2) G7F-DA2V
Digital amount 0 outputs analog amount 0V, 4000 does 10V. Digital input 1 equals to 2.5mV of analog amount.
D/A conversion characteristics (Current output)
D/A conversion characteristics (Current output)
Analog output voltage
10V
5V
0V
0
2000 4000
Digital input value
Analog output voltage
20042000 2001
2002
2003
Digital input
2005
5.0050
5.0025
2.5
D/A conversion characteristics (Current output)
A
nalog output current
20
10
0㎃
0V
0 2000 4000
Digital input value
A
nalog output current
2004
2000 2001 2002 2003
Digital input
2005
10.005
10.000
5
Analog output voltage
20mA
12mA
4mA
0
2000 4000
Digital input value
A
nalog output voltage
20042000 2001
2002
2003
Digital input
2005
12.006
12.000
6.25