Chapter 7. Usage of Various Functions
7-67
.
7) Program example
(1) Program which controls speed of inverter by analog output current (or voltage) of 5 steps (0 ~ 20mA /0~10V)
a) Program explanation (0 channel of the expansion module no.1)
- When %QX0.0.0 is On, 2000(10 /5V) is output.
- When %QX0.0.1 is On, 2400(12 /6V) is output.
- When %QX0.0.2 is On, 2800(14 /7V) is output.
- When %QX0.0.3 is On, 3200(16 /8V) is output.
- When %QX0.0.4 is On, 3600(18 /9V) is output.
b) System configuration
Main unit Analog output module Digital expansion module
c) Program