iS7 Ethernet Option Manual
14
(8) Para Status (COM-30~38)
This parameter is not used in case of Modbus TCP.
This parameter appears only when the set value of the Input Instance
(COM-17) in the EtherNet/IP is 4 or above.
COM-30 Para Status Num cannot be set up but the number of the set
up parameters of the instance is shown. Enter the address of the
inverter data at the same number as that of the said parameters in the
COM-31~38.
(9) Para Control (COM-50~58)
This parameter is not used in case of Modbus TCP.
This parameter appears only when the set value of the Output Instance
(COM-18) in the EtherNet/IP is 4 or above.
COM-50 Para Ctrl Num cannot be set up but the number of the set up
parameters of the instance is shown. Enter the address of the inverter
data, which will make use of the reference data of the Client (Originator),
at the same number as that of the said parameters in the COM-51~58.
(10) Comm UpDate (COM-94)
At power on, the Option Parameters are expressed by the values set up
in the Option, however, not reflected immediately when set up.
If the Comm Update is set to Yes,’ this value is reflected on the
Modbus/TCP communication card and only this card will be restarted.
Set
Value
Input
Instance
Data
Size
The number
of Parameter
0
20
4
X
1
21
4
X
2
100
4
X
3
101
4
X
4
121
2
1
5
122
4
2
6
123
6
3
7
124
8
4
8
125
10
5
9
126
12
6
10
127
14
7
11
128
16
8