iS7 Ethernet Option Manual
11. Lost Command
(1) Inverter Keypad Parameter
"None"
"Free-Run"
"Dec"
"Hold Input"
"Hold Output"
"Lost Preset"
If a Lost Command occurs,
sets up the Inverter action.
(Note1)
Sets up Lost Command
occurrence time
Sets up speed of Lost
Preset
(Note1) Lost Command Mode
Maintains the previous status.
Lost Command Trip occurs and Free Run stopped.
Lost Command Trip occurs and stops by Trip
deceleration time.
Lost Command Warning occurs and operates by the
previous operation reference.
Lost Command Warning occurs and operates at the
previous operation speed.
Lost Command Warning occurs and operates at the
speed set up in the PRT-14.
(2) Modbus TCP Lost Command Status
If the Modbus TCP receives no data from Client for 100msec, the
Option becomes Lost Command status, and after the time set up in the
PRT-13, the Inverter operates according to the settings in the PRT-12.