iS7 Ethernet Option Manual
36
Drive Fault Reset
At 0 1 (FALSE TRUE), the Drive Fault Reset gives TRIP RESET
reference to Inverter. Overwriting 1 (TRUE) on 1 (TRUE) does not
generate RESET reference to the Inverter trip. To send RESET
reference from Option to Inverter in 1 (TRUE) status, write 0 (FAULT)
and then write 1(TRUE) again.
Service
Service
Code
Definition
Support
for Class
Support
for Instance
0x0E
Get Attribute Single
No
Yes
0x10
Set Attribute Single
No
Yes
AC Drive Object (Class 0x2A, Instance 1)
Attribute
Attribute
ID
Access
Attribute
Name
Range
Definition
3
Get
At Reference
0
Means that the output
frequency has not
reached the set up
frequency, yet.
1
Means that the output
frequency has reached
the set up frequency.
4
Not
suppor-
ted
Net Reference
-
-
6
Get
Drive Mode
(Note1)
0
Vendor Specific Mode
1
Open Loop
Speed(Frequency)
2
Closed Loop Speed
Control
3
Torque Control
4
Process Control (e.g. PI)