iS7 Ethernet Option Manual
37
Attribute
ID
Access
Attribute
Name
Range
Definition
7
Get
SpeedActual
0~
24000
Displays present output
frequency in [rpm] unit.
8
Get/Set
Speed Ref
0~
24000
Give reference on the
target frequency in [rpm]
unit. For this, the DRV-07
Freq Ref Src must have
been set up to FieldBus.
9
Get
Actual Current
0~111.
0 A
Monitors present current
by 0.1 A unit basis.
29
Get
Ref.From
Network
0
The frequency reference
source is not the
DeviceNet
communication.
1
The frequency reference
source is the DeviceNet
communication.
100
Get
Actual Hz
0~400.
00 Hz
Monitors present
operating frequency by Hz
unit.
101
Get/Set
Reference Hz
0~400.
00 Hz
When the DRV-07 Freq
Ref Src is set to
8.FieldBus, the reference
frequency can be set up
through communication.
102
Get/Set
Acceleration
Time
(Note2)
0~600
0.0 sec
Set-up/monitor Inverter
acceleration time.
103
Get/Set
Deceleration
Time
(Note3)
0~600
0.0 sec
Set-up/monitor Inverter
deceleration time.
(Note1) Related with the DRV-10 Torque Control and APP-01 App mode.
If the DRV-10 Torque Control is set to Yes, the Drive Mode
becomes “Torque Control, and if the APP-01 App mode is set to
Proc PID, MMC, the Drive Mode becomes “Process Control
(e.g.PI).
(Note2) DRV-03 Acc Time value.