iS7 Ethernet Option Manual
9
7. Ethernet Option and Related Keypad Parameters
The functions below are the inverter parameters which shows the
information related with the Modbus TCP and EtherNet/IP. In the parameter
column, the M stands for the parameters used for Modbus TCP, and E
stands for the parameters used for EtherNet/IP.
Related keypad parameter with iS7 Ethernet
Code
Number
Parameter Name
Default
Set
value
Description
Pro-
tocol
CNF-30
Option-1 Type
-
-
Indicates name of the
communication card installed in
the inverter (Ethernet).
M/E
COM-06
FBus S/W Ver
-
-
Indicates version of the
communication card installed in
the inverter.
M/E
COM-09
FBus Led
-
-
Shows the ON/OFF data of the
LED on the Ethernet
communication card.
M/E
COM-10
Opt Parameter1
192
0~255
Sets up the IP Address.
M/E
COM-11
Opt Parameter2
168
0~255
COM-12
Opt Parameter3
0
0~255
COM-13
Opt Parameter4
101
0~255
COM-14
Opt Parameter5
255
0~255
Sets up the Subnet Mask.
M/E
COM-15
Opt Parameter6
255
0~255
COM-16
Opt Parameter7
255
0~255
COM-17
Opt Parameter8
0
0~255
COM-18
Opt Parameter9
192
0~255
Sets up the Gateway Address.
M/E
COM-19
Opt Parameter10
168
0~255
COM-20
Opt Parameter11
0
0~255
COM-21
Opt Parameter12
10
0~255
COM-22
Opt Parameter13
0
0
Sets up the Ethernet
communication rate.
M/E
COM-23
Opt Parameter14
1
0~11
CIP Input Instance
E
COM-24
Opt Parameter 15
1
0~11
CIP Output Instance
E

Table of Contents