iS7 Ethernet Option Manual
18
Write Multiple Register
The function used to change from 1 to 16 of the Inverter (Server) data
consecutively.
Constitution of the frame requested from Client to Server;
Constitution of the frame sent from Server to Master in response;
Requested Frame
Length
Value
Function code
1bytes
0x10
Comm. address
2bytes
0x0000 ~ 0xFFFF
The number of
data to revise
2byte
1~16
(LSIS Inverter standard)
Byte Count
1byte
2 X The number of data
Data value to
revise
The number
of data
x 2 bytes
Data to revise
Response Frame
Length
Value
Function Code
1 Bytes
0x10
Comm. address
2 Bytes
0x0000 ~ 0xFFFF
The number of
data to revise
2 Bytes
1~16
(LSIS Inverter standard)