LSIS H100 Quick Start Guide
1 LS H100 Quick Start Guide
Rev I_6-19-2017
1. H100 Basic Setup Parameters
The basic drive and motor parameters are shown in Table 1. Set the parameters according to your application.
Table 1. H100 Basic Setup Parameters
Note: Many applications will not require changes to the basic setup parameters from their default values.
1.1 H100 Recommended Additional Parameter Changes
The H100 drive has some default settings the user may want to change to obtain better protection of the
drive/motor and the application. These changes are recommended, but not needed for all applications.
Auto Reset
Program CON 71 bit 3 to High State (0100).
Program PRT 08 (Reset/Restart after a fault) to “1” (Yes).
Program PRT 09 (Number of Retries) to a number between 0 -10.
Program PRT 10 (Auto Reset Time) to desired time to allow cause of fault to clear and safe starting.
Start on Power Loss
Program ADV 10 (Power on Start) to “1” (Yes).
Phase Loss
Program PRT 05 (Phase Loss) to detect input and/or output phase loss.
Note: This parameter is displayed as DIP switches on the H100. Left bit is the Input, Right bit is the Output.
2. HP to kW Conversion Table
Use the following conversion table to enter the motor HP. Select the closest size the drive allows in kW (motor
power is in kW on most LSIS drives)

Other manuals for LSIS H100

Questions and Answers:

LSIS H100 Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control MethodV/F Control, Sensorless Vector Control
Cooling MethodForced Air Cooling
AltitudeUp to 1000m without derating
Input Voltage380V - 480V
Input Frequency50Hz/60Hz
Output Voltage0 to Input Voltage
Output Frequency0.1 to 400Hz
Protection FunctionsOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
CommunicationRS485 (Modbus RTU)
Operating Temperature-10 to 50°C
Storage Temperature-20°C ~ +65°C
Humidity5% to 95% RH (non-condensing)

Summary

1. H100 Basic Setup Parameters

1.1 H100 Recommended Additional Parameter Changes

Details recommended parameter adjustments for auto reset, power loss start, and phase loss detection.

2. HP to kW Conversion Table