Chapter 3. Standard Specification
3-1
Chapter 3. Standard Specification
3.1 General Standards
iXP Series general standard is as follows.
No.
Category
Standard
Related standard
1
Ambient
operating
temperature
0℃∼+50
-
2
Storage
temperature
-20℃∼+60
-
3
Operating
humidity
1085%RH, non-condensing.
-
4
Storage
humidity
1085%RH, non-condensing.
-
5
Vibration
resistance
Occasional vibration
count
-
Frequency
Acceleration
Amplitude
10 times each
in X, Y and Z
direction
IEC 61131-2
5 f < 9
-
3.5 mm
9 f 150
9.8
-
Continuous vibration
Frequency
Acceleration
Amplitude
5 f < 9
-
1.75 mm
9 f 150
4.9
-
6
Shock
endurance
* Maximum shock acceleration: 147 (15G)
* Duration time: 11
* Pulse wave: half sine pulse (3 times each in X, Y and Z directions)
IEC 61131-2
7
Noise
Immunity
Square wave
Impulse noise
AC: ±1,500V
DC: ±1,000V
LSIS Standard
Electrostatic
discharge Immunity
±6 kV (Discharge by contact)
±8kV (Air discharge)
IEC 61131-2
IEC 61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1000 MHz, 10 V/m
IEC 61131-2
IEC 61000-4-3
Fast transient &
Burst noise
Category
Power module
Communication
interface
IEC 61131-2
IEC 61000-4-4
Voltage
2 kV
1 kV
8
Environment
Free from corrosive gases and excessive dust
-
9
Operating
height
Up to 2,000m (6,562 ft)
-
10
Pollution degree
2 or less
-
11
Cooling method
Self-cooling
-