Chapter 10. Installation and Wiring
10-7
The power terminal should have the following specification.
The power cable should have the following specification.
Type
Cable specification (Unit: )
Power and protection ground
1.5 (AWG16) ~ 2.5 (AWG12)
Remark
(1) For installations where there is voltage drop, it is recommended to use stranded wire with a cross sectional area
1.5~2.5.
(2) It is recommended that cable connections are twisted and secure. Short cable runs are also recommended
Between the point of supply and the XGT panel.
(3) For safety reasons it is recommended that you use color coded outer sheaths on the conductors to aid safe
terminations.
Follow local regulations when making electrical connections.
Wiring of power is as follows.
Less than
6.00mm
Less than
6.00mm
Ø 3.2
Ø 3.2
DC Power connection