7. Function List
7-20
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
I53
[Frequency
detection
bandwidth]
select] are set to 0-4.
It cannot be set greater than
F21 [Max frequency].
10.0 O
I54
[Multi-function
output
terminal
select]
0/17
0 FDT-1
12 O
1 FDT-2
I55 [Multi-function
relay select]
2
FDT-3
17
3 FDT-4
4
FDT-5
5 Overload {OL}
6
Inverter Overload {IOL}
7 Motor stall {STALL}
8
Over voltage trip {OV}
9 Low voltage trip {LV}
10
Inverter heatsink overheat
{OH}
11 Command loss
12
During run
13 During stop
14
During constant run
15 During speed searching
16
Wait time for run signal input
17 Fault relay output
I56
[Fault relay
output]
0/7 When
setting
the
H26
[Number
of auto
restart
try]
When
the trip
other
than
low
voltage
trip
occurs
When
the low
voltage
trip
occurs
2 O
Bit 2 Bit 1 Bit 0
0
-
-
-
1 - -
2
-
-
3 -
4
-
-
5 -
6
-
7