4. Error Code List
45
Project data is not
downloaded. Please
download project
again.
The project data was not downloaded
normally because of communication
error. Check the connection status of
communication cable and If this
symptom is repeated, contact Customer
Service Center.
Failed to read
Version information
file. Please
download project
again.
There is version information file but when
it can’t read file normally because of the
device error, downloading is stopped
because it doesn’t know version. If this
symptom is repeated, contact Custom
Service Center
Project
download
from
USB storage
device
Cannot find project
data in USB Storage
There is no USB or device status of USB
is not good or project is not saved
properly.
Project information
file is not in USB
Storage.
The project is not saved normally in the
USB. Check whether there is XP_Project
folder and [project name].inf in the USB
or not.
Failed to read
project information
file.
It can’t read project information file
because the project is not saved in the
USB normally. Save the project again
from XP-Builder to the USB.
Device type is not
matched.
The connected device type is not same
as the device type set in the project in
the USB. In case of this, project can’t be
downloaded into the device. Edit the
project again or download according to
the connected device.
Cannot read user
password.
Information about the password can’t be
red because of the device error. If this
symptom is repeated, contact Customer
Service Center.
When saving the project, the password
inputted by user is not same as present
connection password. Input correct
password and save the project.
Cannot read XGT
Panel software
version.
There is version information file but when
it can’t read file normally because of the
device error, downloading is stopped
because it doesn’t know version. If this
symptom is repeated, contact Customer
Service Center.
XGT Panel software
is old version.
Please update XGT
Panel.
The version of XP-Builder where project
is saved is not compatible with present
XGT Panel. Update the XGT Panel.
XP-Builder is old
version. Please
update XP-Builder.
The version of XP-Builder where project
is saved is not compatible with present
XGT Panel. Update the XGT Panel.