Faults
MXD70 Auxiliary mA Input
Setup and Operating Guide
- 43 -
Faults
Calculation Errors
E400 C1 Calculation Over Range
E410 C2
The Calculation reading is greater than the specified upper limit, check channel
settings, calculation configuration, sensor condition and connections. If the
message persists please consult with your supplier.
E401 C1 Calculation Under Range
E411 C2
The Calculation reading is less than the specified lower limit, check channel
settings, calculation configuration, sensor condition and connections. If the
message persists please consult with your supplier.
E402 C1 Calculation Setup Checksum
E412 C2
The Setup for this Calculation has become corrupted. Check and correct the
calculation settings and turn the unit off and on again. If the message persists
please consult with your supplier.
E403 C1 Calculation Store A Checksum
E413 C2
The Store A Save for the channel associated with this calculation has become
corrupted. Check the calculation’s settings in the calculation menu and then save
the settings again in the Channel's Store A in the Save/Restore menu.
E404 C1 Calculation Store B Checksum
E414 C2
The Store B Save for the channel associated with this calculation has become
corrupted. Check the calculation’s settings in the calculation menu and then save
the settings again in the Channel's Store B in the Save/Restore menu.
E405 C1 Calculation SD Card Checksum
E415 C2
The SD Card store from which this Calculation was restored from has become
corrupted. Check the Calculation's settings in the Calculation menu and then save
the settings again to the SD card store.