EasyManuals Logo

Lumel ND20 User Manual

Lumel ND20
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
38
Device
address
Function Register
address
Number of
registers
CRC
Control sum
B1 B0 B1 B0
01 03 1B 58 00 04 C3 3E
Request:
Device address
Function
Number of
baytes
Value from
register
1B58
(7000)
Value
from
register
1B59
(7001)
Value from
register
1B5A (7002)
Value from
register
1B5B
(7003)
CRC
Con-
trol
sum
B3 B2 B1 B0 B3 B2 B1 B0
01 03 08 41 20 00 00 42 C8 00 00 E4 6F
Response:
Example 2
. Readout of 2 registers 32-bit of float type as 2 registers
16-bits, starting with the register with the 1B58h (7000) address
- register values 10, 100.
Example 3 . Readout of 2 registers 32-bit of float type as 2 registers
16-bit, starting with the register with the 1770h (6000) address -
register values 10, 100.
Request
Device
address
Function Register
address
Number of
registers
CRC
Control sum
B1 B0 B1 B0
01 03 17 70 00 04 4066
Device
address
Fun-
ction
Num-
ber of
bytes
Register
address
0FA0
(4000)
Number of
registers
0FA1 (4001)
CRC
Control
sum
B1 B0 B1 B0
01 03 04 00 0A 00 64 E4 6F
Response: