62
Measured
value
Indication
range*
Measuring
range
L1 L2 L3
S
Basic
error
Current In
1 A
5 A
0.00 ... 12 kA
0.00 ... 60 kA
0.002 ... 1.200 A~
0.010 ... 6.000 A~
l l l
±0.2% r
Voltage L-N
57.7 V
230 V
0.0 ... 280 kV
0.0 ... 1.104 MV
2.8 ... 70.0 V~
11.5 ... 276 V~
l l l
±0.2% r
Voltage L-L
100 V
400 V
0.0 ... 480 kV
0.0 ... 1.92 MV
5 ... 120 V~
20 ... 480 V~
l l l
±0.5% r
Frequency 47.0 .. 63.0 Hz 47.0...63.0 Hz
l l l
±0.2%mv
Active power
-9999 MW .. 0.00 W
.. 9999 MW
-1.65 kW...1.4
W...1.65 kW
l l l l
±0.5% r
Reactive power
-9999 Mvar .. 0.00
var ... 9999 Mvar
-1.65 kvar...1.4
var...1.65 kvar
l l l l
±0.5% r
Apparent power 0.00 VA .. 9999 MVA 1.4 VA...1.65 kVA
l l l l
±0.5% r
Power factor PF -1 .. 0.. 1 -1...0...1
l l l l
±1% r
Tangent j factor
-10.2...0...10.2 -1.2...0...1.2
l l l l
±1% r
Cosinus
j
-1... 1 -1... 1
l l l l
±1% r
j
-180 ... 180 -180 ... 180
l l l
±0.5% r
Imported active
energy
0 .. 99 999 999.9
kWh
l
±0.5% r
Exported active
energy
0 .. 99 999 999,9
kWh
l
±0.5% r
Reactive inductive
energy
0 .. 99 999 999.9
kvarh
l
±0,5%
Reactive
capacitive energy
0 .. 99 999 999.9
kvarh
l
±0,5%
THD 0 .. 100% 0 .. 100%
l l l
±5%
10. TECHNICAL DATA
Measuring ranges and admissible basic errors
Table 13
* Depending on the set tr_U ratio (ratio of the voltage transformer: 0.1...4000.0)
and tr_I ratio (ratio of the current transformer: 1...10000)
r - of the range
mv - of the measured value
Caution! For the correct current measurement the presence of a voltage
higher than 0.05 Un is required at least in one of the phase