43
1010 R
Hour * 100 + minute of archived mean power with
number NrBL + 1
1011 R
Value of archived mean power with number NrBL + 1
float type – 4 bytes in sequence 3-2-1-0
1012 R
... ... ...
1073 R Year of archived mean power with number NrBL + 14
1074 R
Month * 100 + day of archived mean power with number
NrBL + 14
1075 R
Hour * 100 + minute of archived mean power with
number NrBL + 14
1076 R
Value of archived mean power with number NrBL + 14
float type – 4 bytes in sequence 3-2-1-0
1077 R
Register
address
Ope-
ra-
tion
Range Description By default
4000 RW 0...60000 Protection - password 0
4001 RW 0...900 [s]
Interlocking time of the renewed
switching of the relay output on
0
4002 RW
0...1440
[
o
/oo]
Ordered mean power *10 1000
4003 RW 1..10000 Current transformer ratio 1
4004 RW 1..40000 Voltage transformer ratio *10 10