52
6042/7042 7521 R Mean 3-phase voltage V
√
x x
6044/7044 7522 R Mean 3-phase current A
√ √
x
6046/7046 7523 R 3-phase active power
(P1+P2+P3)
W
√ √
x
6048/7048 7524 R 3-phase reactive power
(Q1+Q2+Q3)
var
√ √
x
6050/7050 7525 R 3-phase apparent power
(S1+S2+S3)
VA
√ √
x
6052/7052 7526 R Mean power factor (PF) -
√ √
x
6054/7054 7527 R Mean Tg j factor of phase L1 -
√ √
x
6056/7056 7528 R Frequency Hz
√ √
x
6058/7058 7529 R Phase-to-phase voltage L1-2 V
√ √
x
6060/7060 7530 R Phase-to-phase voltage L2-3 V
√ √
x
6062/7062 7531 R Phase-to-phase voltage L3-1 V
√ √
x
6064/7064 7532 R Mean phase-to-phase
voltage
V
√ √
x
6066/7066 7533 R 3-phase 15, 30, 60 minutes’
active Power (P1 + P2 + P3)
W
√ √ √
6068/7068 7534 R Harmonic U1 / THD U1 V / %
√
x
√
6070/7070 7535 R HarmonicU2 / THD U2 V / %
√
x x
6072/7072 7536 R Harmonic U3 / THD U3 V / %
√
x x
6074/7074 7537 R Harmonic I1 / THD I1 A / %
√
x
√
6076/7076 7538 R Harmonic I2 / THD I2 A / %
√
x x
6078/7078 7539 R Harmonic I3 / THD I3 A / %
√
x x
6080/7080 7540 R Cosinus of angle between
U1 and I1
-
√
x x
6082/7082 7541 R Cosinus of angle between
U2 and I2
-
√
x x
6084/7084 7542 R Cosinus of angle between
U3 and I3
-
√
x x