CDA3000 Operation Manual
3-3
3 Electrical installation
1
2
3
4
5
A
DE
EN
FR
IT
ES
FR
3.2 Grounding lead
connection
Figure 3.2 Star configuration layout of the grounding lead
Step Action
Comment: PE mains connection
to VDE 0100 part 540
1
Ground every inverter module!
Connect terminal X1/
in star
configuration to the PE-rail (main
ground) in the switch cabinet.
Mains connection < 10 mm²
:
Use grounding lead (PE) cross section
min. 10 mm²
or
2 wires with cross-
section of mains leads.
Mains connection > 10 mm²:
Use grounding lead (PE) cross section
according to cross-section of mains
leads.
2
Also connect the grounding lead con-
nections of all other components,
such as the line choke, filter, etc., in
star configuration to the PE-rail
(main ground) in the switch cabinet.
Note the following points:
The grounding lead must be laid out in star configuration to conform
to the EMC standards.
The backing plate must be well grounded.
The motor cable, mains lead and control cable must be laid
separately from each other.
Avoid loops, and lay cable over short distances.
The operational leakage current is > 3.5 mA.
,,
,,
,,
W1
V2
W2
U2
U1
V1
,,
,
,,
,,
,
W1
V2
W2
U2
U1
V1
,,
,,
W1
V2
W2
U2
U1
V1
PE