5-4
CDA3000 Operation Manual
5 Diagnosis/Fault rectification
5.7 Reset
Device reset
The inverter module can be reset by way of the
Reset button. This triggers a system initialization
and processor reset.
Parameters changes only in the RAM, i.e. not
backed-up by parameter 150-SAVE, are reset to the
original - last saved - value.
Figure 5.1 Reset button (1)
Parameter reset
In PARA menu of KEYPAD: Press the two cursor keys to reset the parame-
ter currently being edited to the factory defaults.
In D
RIVEMANAGER: In the edit window of the parameter editor choose the
“Standard” button.
Factory setting
Press both cursor keys simultaneously during inverter module power-up
to reset all parameters to their factory defaults and the system is reinitial-
ized.
Parameter 004-PROG = 1 can also be set. This resets all parameters of
the active user data set to their factory defaults. Then the factory setting is
backed-up by parameter 150-SAVE = BUSY.
Note: Attention! The factory setting loads application data set 1
(traction and lifting drive, configuration 1). Observe the termi-
nal assignment and functionality of the inverter module in this
operation mode, or load your own user data set.