CDA3000 Operation Manual
A-5
1
2
3
4
5
A
DE
EN
FR
IT
ES
FR
A.2 Ambient
conditions
Feature Inverter module
Tempera-
ture range
in operation
-10 ...45 ° C (BG1 ... BG5)
0 ... 40 ° C (BG6 ... BG8)
with power reduction up to 55 ° C
in storage -25 ... +55 °C
in transit -25 ... +70 °C
Relative air humidity 15 ... 85 %, condensation not permitted
Mechani-
cal strength
to IEC
68-2-6
in stationary
operation
Vibration: 0.075 mm in frequency range 10 ... 58 Hz
Shock: 9.8 m/s
2
in frequency range >58 ... 500 Hz
in transit
Vibration: 3.5 mm in frequency range 5 ... 9 Hz
Shock: 9.8 m/s
2
in frequency range >9 ... 500 Hz
Protection
Device menu IP20 (NEMA 1)
Cooling
method
Cold plate: IP20
Push-through heat sink: IP54 (3 ...15 kW)
Push-through heat sink: IP20 (22 ... 37 kW)
Touch protection VBG 4
Mounting height
to 1000 m above MSL, over 1000 m MSL with power
reduction of 1% per 100 m, max. 2000 m above MSL