3-4
CDD3000-HF Operation Manual
3 Installation
3.2 Grounding lead
connection
Figure 3.1 Star configuration layout of the grounding lead
Step Action
Note: PE mains connection
to VDE 0100 part 540
1
Ground every CDD3000-HF drive
controller! Connect terminal X1 /
(next to the power connection) in star
configuration to the PE-rail (main
ground) in the switch cabinet.
Mains connection < 10 mm²:
Grounding lead cross-section min.
10 mm²
or use 2 wires with cross-
section of mains leads.
Mains connection > 10 mm²:
Use grounding lead (PE) cross
section according to cross-section
of mains leads.
2
Also connect the grounding lead
connections of all other components,
such as the line choke, filter, heat sink,
etc., in star configuration, to the PE-rail
(main ground) in the switch cabinet.
Note the following points:
The grounding lead must be laid out in star configuration to conform
to the EMC standards.
The backing plate must be well grounded.
The motor cable, mains lead and control cable must be laid
separately from each other.
Avoid loops, and lay cable over short distances.
The operational leakage current is > 3.5 mA.