4-2
CDD3000-HF Operation Manual
4 Commissioning
4.1 Choice of
commissioning
4.2 Serial
commissioning
Apply this mode of commissioning when you want to commission several
identical drives (i.e. serial commissioning). The same HF drive controller
type and the same motor must be used for each drive in an identical
application.
If you already have a complete data set, skip the paragraphs headed
"Saving a data set from the device to a file"
(with DRIVEMANAGER, steps
1-4) and
"Saving a data set to a S
MART
C
ARD
"
(with KEYPAD).
A test run is essential, see section 4.4.
4.2.1 Serial
commissioning
with
D
RIVEMANAGER
Precondition:
All CDD3000-HFs are fully connected.
The first drive is already fully commissioned.
A PC with installed D
RIVEMANAGER user software (V3.4 or higher) is
connected.
Mode of commissioning Commissioning steps
Continued
on
Project planning and commissioning are
already complete.
Loading of an existing data set.
Serial commissioning Page 4-2
Initial project planning and commissioning
of the drive system
Initial commissioning Page 4-6
Project planning and basic setting of the
drive system have been carried out.
Test run Page 4-18