CDD3000-HF Operation Manual
4-3
4 Commissioning
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
Note: For more information refer to the DRIVEMANAGER Manual.
Step Action Comments
1
Connect your PC to the CDD3000-HF
of the first drive and switch on the
power to the CDD3000-HF.
Use a standard serial cable (9-pin
D-SUB, pin-and-socket) e.g. LUST
accessory CCD-SUB90x .
2
START DriveManager.
Automatically connects to the linked
CDD3000-HF.
If the connection fails, check the bus settings in the Communication > Bus
Configuration menu and try again by clicking on the icon.
3
Save the current settings by clicking
on the icon ,
either in the parameter database
(directory: c:/../userdata) of the
D
RIVEMANAGER or to a floppy disk (a:/).
Clicking on the icon always saves the
current settings of the connected
device. Assign the file a name of your
choice.
If you are using the “Positioning, fully
programming” preset, also save the
positioning programs and data.
1)
4
Disconnect with
5
Connect your PC to the CDD3000-HF of the next drive and switch on the
power to the CDD3000-HF.
6
Click on the icon to make a connection between the DRIVEMANAGER
and the newly connected device.
7
Choose the icon to load
the data set saved in step 3 into the
device (select all files).
The data set is stored in the device.
The selection box shows all the stored
files in the data set.
8
Save the setting by clicking on the “Save setting in device” button.
Repeat steps 5 ... 8 on each additional CDD3000-HF.
1) For details of save operation see Section 4.3.9.
Remember to save the
setting.
Saving a data set from the
device to a file
Load data set from file into
device