3-18
CDD3000-HF Operation Manual
3 Installation
3.6.1 Specification of
control
connections
No. Des. Specification Isolation
Analog
Inputs
1
2
3
4
ISA00+
ISA00-
ISA00: U
IN
= ± 10 V DC, resolution 12-bit,
sampling time 1 ms (special function 125 µs)
ISA01+
ISA01-
ISA01: U
IN
= + 10 V DC, resolution 10-bit,
sampling time 1 ms
Tolerance: ± 1% of meas.
24 V digital input, PLC-compatible
Switching level Low/High: <4.8 V / > 8 V DC
Sampling time 1 ms
•R
IN
= 110 k
Digital
Inputs
8
9
10
11
12
ISD00
ISD01
ISD02
ISD03
ISD04
ISD00-ISD02: Frequency range < 500 Hz,
sampling time 1ms
ISD03-ISD04: Frequency range < 500 kHz,
sampling time 1ms (special functions < 2
µs)
PLC-compatible
Switching level Low/High: <5 V / > 18 V DC
•I
max
(at 24 V) = 10 mA
•R
IN
= 3 k
7 ENPO Hardware enable of power stage = High level
Specification as ISD00
Digital
Outputs
14 OSD00 Short-circuit-proof
PLC-compatible, sampling time 1 ms
•I
max
= 50 mA, high-side driver
Protection against inductive load