CDD3000-HF Operation Manual
4-19
4 Commissioning
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
1. Set power stage enable ENPO
High level at terminal 7 (X2)
Pay attention to the time response of the inputs.
2. Control with D
RIVEMANAGER:
Set the ENPO input, select “Speed control” and start the drive, e.g. at
reference speed 100 rpm.
Check the drive response
Now you can assess the drive response with the aid of step responses,
which can be recorded using the D
RIVEMANAGER's digital scope function.
Select the following four recording variables:
- 0: Speed: Reference
- 1: Speed: Actual
- 2: Torque: Reference
- 3: Torque: Actual
t
0
1
0
1
0
1
2 ms
4 ms
ENPO input
Start input
Device status:
“Loop control active”
DRIVEMANAGER
Open-loop control
or:
Active device > Open-loop
control> Basic operation
modes
DRIVEMANAGER
Digital scope
or:
Active device > Monitoring >
Quickly changing digital scope