Por ejemplo.
Parámetro 47 "Potencia Motor" = 1000 watts
parámetro 64 "Umbral Minimo %" = 50%
parámetro 72 "Pres.Instalacion" = 2,5 bar [36,26 psi]
El valor de potencia para apagar la segunda bomba es igual
a 50% de 1000 W, entonces: 500 W. Así que si la presión es
mayor o igual a 2,5 bar [36,26 psi] y la potenica es inferior a
500 vatios el inversor apagará la segunda bomba.
Eg.
Parameter 47 "Motor Power" = 1000 watts
parameter 64 "MinTresholdPar" = 50%
parameter 72 "System Pressure" = 2.5 bar [36.26 psi]
The power value to switch off the second pump is equal to
50% of 1000 watts then: 500 watts. So that if pressure is
greater or equal to 2.5 bar [36.26 psi] and power is less
than 500 watt the drive switch off the second pump.