EasyManua.ls Logo

MAKELSAN PowerPack SE 3 kVA - Frequency Converter Mode Setting

Default Icon
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UDD-SD-116/ Release Date: 31.12.2014/Rev No: 1/Rev. Date: 27.04.2015 30
4. Exit from the setting interface. Press and hold function setting key for more than half a
second (less than 2 seconds), exit from the setting interface and return to main interface.
4.6.5 Frequency Converter Mode Setting
1. CUCF mode only can be set in STDBY mode. In STDBY mode, enter the setting interface. Press
and hold the function setting key for more than 2 seconds, then come to setting
interface, Press and hold the inquiring key ( , ) for more than half a second(less
than 2 seconds), select the function setting, choose battery voltage setting interface, at
the moment, the letters “CF” will flash.
2. Enter the CF setting interface. Press and hold the function setting key for more than half
a second(less than 2 seconds), then come to setting interface of CF, at this time, the letters “CF”
will not flash any more. The “ON” (or OFF) will flash. Press and hold the inquiring key ( ,
) for more than half a second (less than 2 seconds) to determine whether the CF
function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”.
It can be determined by yourself.
3. Confirm the CF selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the CF setting function
is completed and the “ON” or “OFF” will light without flash.
4. Exit from the setting interface. Press and hold function setting key for more than 2
seconds, exit from the setting interface and return to main interface.
5. After setting CF at “ON”, UPS would be back in STDBY Mode. The default value of CF is OFF.

Related product manuals