120 Part Number: 000015431 Rev01 5/19
Harvest valve failure
Measured in the harvest cycle
a. High pressure will be higher
b. Low pressure will be lower than published.
Fan cycling control failure page 154
Measured in the harvest cycle
a. Condenser fan motor does not cycle off when
pressure is below fan cycle control cut out
setting .
Accumulator failure page 165
Measured in the freeze cycle
The suction line temperature between the
accumulator and compressor does not increase 20+0F
within 6 minutes of a freeze cycle . The test must be
run after a harvest cycle has been completed.

Table of Contents

Other manuals for Manitowoc Indigo NXT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo NXT Series and is the answer not in the manual?

Manitowoc Indigo NXT Series Specifications

General IconGeneral
ModelIndigo NXT Series
Ice ProductionVaries by model
Ice StorageVaries by model
Energy EfficiencyEnergy Star certified models available
RefrigerantR290 (varies by model)
Cooling SystemAir-cooled or water-cooled (varies by model)
Condenser TypeAir-cooled, Water-cooled, or Remote
Touch DisplayYes, with intuitive interface
ControlCleaning Alerts
FeaturesSelf-cleaning, remote monitoring, energy-saving modes
Power SupplyVaries by model (typically 115V or 208-230V)
Dimensions (H x W x D)Varies by model
WeightVaries by model

Related product manuals