Part Number: 000015431 Rev01 5/19 135
MAIN FUSE
FUNCTION
The control board fuse stops ice machine operation if
electrical components fail, causing high amp draw.
SPECIFICATIONS
The main fuse is 250 Volt, 6.3 amp.
n
Warning
High (line) voltage is applied to the control board
(terminals #55 and #56) at all times. Removing the
control board fuse or pressing the On/Off button will
not remove the power supplied to the control board.
CHECK PROCEDURE
1. If control board lights are energized the fuse is good.
n
Warning
Disconnect electrical power to the entire ice machine
before proceeding.
2. Remove the fuse. Check for continuity across the fuse
with an ohmmeter.
Reading Result
Open (OL) Replace fuse
Closed (O) Fuse is good

Table of Contents

Other manuals for Manitowoc Indigo NXT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo NXT Series and is the answer not in the manual?

Manitowoc Indigo NXT Series Specifications

General IconGeneral
ModelIndigo NXT Series
Ice ProductionVaries by model
Ice StorageVaries by model
Energy EfficiencyEnergy Star certified models available
RefrigerantR290 (varies by model)
Cooling SystemAir-cooled or water-cooled (varies by model)
Condenser TypeAir-cooled, Water-cooled, or Remote
Touch DisplayYes, with intuitive interface
ControlCleaning Alerts
FeaturesSelf-cleaning, remote monitoring, energy-saving modes
Power SupplyVaries by model (typically 115V or 208-230V)
Dimensions (H x W x D)Varies by model
WeightVaries by model

Related product manuals