98 Part Number: 000015431 Rev01 5/19
DIAGNOSING A CONDENSING UNIT
THAT WILL NOT RUN
If the ice machine water pump is not energized, refer to
“Diagnosing an Ice Machine that Will Not Run.
1. Verify primary voltage is supplied to the ice machine
condensing unit and the fuse/circuit breaker is closed.
2. Verify the high-pressure control is closed.
3. Verify the low-pressure control is closed.
4. Verify voltage is present at terminals 1 & 2 on the
compressor time delay relay.
5. Verify the time delay period has expired and test for
line voltage at compressor time delay relay terminals
1 & 3.
6. Verify line voltage is present at the contactor coil.
7. Verify the contactor contacts are closed and line
voltage is present across all lines.
8. Refer to compressor diagnostics.

Table of Contents

Other manuals for Manitowoc Indigo NXT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo NXT Series and is the answer not in the manual?

Manitowoc Indigo NXT Series Specifications

General IconGeneral
ModelIndigo NXT Series
Ice ProductionVaries by model
Ice StorageVaries by model
Energy EfficiencyEnergy Star certified models available
RefrigerantR290 (varies by model)
Cooling SystemAir-cooled or water-cooled (varies by model)
Condenser TypeAir-cooled, Water-cooled, or Remote
Touch DisplayYes, with intuitive interface
ControlCleaning Alerts
FeaturesSelf-cleaning, remote monitoring, energy-saving modes
Power SupplyVaries by model (typically 115V or 208-230V)
Dimensions (H x W x D)Varies by model
WeightVaries by model

Related product manuals