152 Part Number: 000015431 Rev01 5/19
LOW PRESSURE CUTOUT (LPCO) CONTROL
FUNCTION
Supplies or interrupts power to the compressor time delay
when suction pressure rises above or falls below setpoint.
The LPCO control is closed at pressures above setpoint and
opens at pressures below setpoint.
Specifications
Cut-Out Cut-In
R404A 12 psig ±3 35 psig ±5
R410A 20 psig ±3 50 psig ±5
CHECK PROCEDURE
Opening the LPCO will initiate the 5 minute compressor
time delay relay. Repeated opening/closing or failure to
close will result in an E01 long freeze error.
CHECK PROCEDURE
1. Connect manifold gauges to ice machine.
2. Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
3. Refer to chart below.
LPCO Setpoint Reading Should Be LPCO Contact Position
Above Cut-In 0 Volts Closed
Below Cut-Out Line Voltage Open

Table of Contents

Other manuals for Manitowoc Indigo NXT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo NXT Series and is the answer not in the manual?

Manitowoc Indigo NXT Series Specifications

General IconGeneral
ModelIndigo NXT Series
Ice ProductionVaries by model
Ice StorageVaries by model
Energy EfficiencyEnergy Star certified models available
RefrigerantR290 (varies by model)
Cooling SystemAir-cooled or water-cooled (varies by model)
Condenser TypeAir-cooled, Water-cooled, or Remote
Touch DisplayYes, with intuitive interface
ControlCleaning Alerts
FeaturesSelf-cleaning, remote monitoring, energy-saving modes
Power SupplyVaries by model (typically 115V or 208-230V)
Dimensions (H x W x D)Varies by model
WeightVaries by model

Related product manuals